DIN Rail Control Processor Crestron DIN-AP2
Connectors, Controls & Indicators
# CONNECTORS
1
,
CONTROLS &
INDICATORS
DESCRIPTION
1 I/O VERSIPORTS 1-8 (1) 9-pin 3.5mm detachable
terminal block comprising (8)
digital input/output or analog
input ports (referenced to GND)
Max Wire Size: 1.5 mm
2
(16 AWG)
Digital Input:
Rated for 0-24 Volts DC
Input Impedance 20k ohms
Logic Threshold: 1.25 Volts
DC
Analog Input:
Rated for 0-10 Volts DC,
protected to 24 Volts DC
maximum
Input Impedance 20k ohms
Digital Output:
250 mA sink from maximum
24 Volts DC, catch diodes
for use with “real world”
loads
Programmable 5 Volts, 2k ohms
pull-up resistor per input
2 PWR LED (1) Green LED, indicates power
supplied to unit via NET port
3 NET LED (1) Yellow LED, indicates
Cresnet bus activity
(Continued on following page)
8 DIN Rail Control Processor: DIN-AP2 Operations & Installation Guide – DOC. 6662A